UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
Safety and
EMC
8.5 Mains Input Electrical Specifications
Item
Input system
Rated input
voltage
Input voltage
Rated
frequency
Input
frequency
Input PF
THDi
8.6 Bypass Input Electrical Specifications
Item
Input system
Rated input
Issue 05 (2018-01-08)
400 kVA
500 kVA
IEC61000-2-2
IEC61000-4-2
IEC61000-4-4
IEC61000-4-5
EN61000-4-3
EN61000-4-6
IEC61000-4-8
400 kVA
500 kVA
Three-phase, four-wire, and PE
380 V AC, 400 V AC, or 415 V AC (line voltage)
80–280 V AC (phase voltage)
At 40° C: The UPS works at full load when the voltage is 187–280 V
AC and is derated to 40% load when the voltage is 187–80 V AC.
At 30° C: The UPS works at full load when the voltage is 176–280 V
AC and is derated to 40% load when the voltage is 176–80 V AC.
50 Hz or 60 Hz
40–70 Hz
> 0.99 (full load)
> 0.98 (half load)
THDi < 3% (full linear load)
THDi < 5% (full non-linear load)
400 kVA
500 kVA
Three-phase, four-wire, and PE
380 V AC, 400 V AC, or 415 V AC (line voltage)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 Technical Specifications
600 kVA
800 kVA
600 kVA
800 kVA
600 kVA
800 kVA
280