UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
Figure 5-38 Confirmation message
Step 4 Check that the load power is stable (that is, no transient surge results in overload, which may
cause the UPS to transfer to bypass mode), and tap Yes.
Step 5 Set Module cycle hiber. period (d) to an integer ranging from 1 to 100. The default value is
30.
----End

5.12.2 WebUI

Procedure
Step 1 On the login page, enter a user name and password, and click Login.
Step 2 Choose Monitoring > Param. Settings > Advanced Param., as shown in
Figure 5-39 Hibernation parameters on the WebUI
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations
Figure
5-39.
267