UPS5000-A-(30 kVA-120 kVA) User Manual
User Manual
Item
THDi
8.6 Bypass Input Electrical Specifications
Item
Input system
Rated input voltage
Rated frequency
Frequency range
Input system
8.7 Battery Specifications
Item
Specifications
Battery voltage
● UPS5000-A-30KTTL/UPS5000-A-40KTTL/UPS5000-A-80KTTL/UPS5000-
● UPS5000-A-60KTTL-H/UPS5000-A-120KTTL-H:
Issue 15 (2022-11-15)
Specifications
● THDi < 3% (linear load)
● THDi < 5% (non-linear load)
Remarks:
1. The preceding specifications are met when the mains input and bypass
input share a power source.
2. The input THDu is less than 1%.
Specifications
Three-phase, four-wire, and PE
380 V AC/400 V AC/415 V AC (line voltage)
50/60 Hz
±6 Hz (adjustable, 0.5–6 Hz, ±2 Hz by default)
The mains input and bypass input can share a power source or use
different power sources.
A-60KTTL/UPS5000-A-120KTTL:
360–528 V DC (12 V batteries, 30–44 batteries, 32 batteries by default)
– 32–44 batteries: The output power is not derated.
– 30 batteries: The output power is derated to 94%.
NOTE
If the MDU and power versions are earlier than V100R002C01SPC007, the battery
voltage is 360–480 V DC (30–40 batteries, 32 batteries by default).
360–528 V DC (12 V batteries, 30–44 batteries, 40 batteries by default)
– 40–44 batteries: The output power is not derated.
– 36 and 38 batteries: The output power in battery mode is derated to 90%.
– 32 and 34 batteries: The output power in battery mode is derated to 80%.
– 30 batteries: The output power in battery mode is derated to 75%.
Copyright © Huawei Digital Power Technologies Co., Ltd.
8 Technical Specifications
149