Bypass Input Electrical Specifications; Battery Specifications - Huawei UPS5000-A-30KTTL User Manual

Hide thumbs Also See for UPS5000-A-30KTTL:
Table of Contents

Advertisement

UPS5000-A-(30 kVA-120 kVA)
User Manual
Item
Rated frequency
Input frequency
Input power factor
THDi
Overvoltage
category

3.6 Bypass Input Electrical Specifications

Item
Input system
Rated input voltage
Rated frequency
Frequency range
Input system
Overvoltage category

3.7 Battery Specifications

Issue 17 (2024-02-21)
Specifications
50/60 Hz
40–70 Hz
> 0.99 at full load; > 0.98 at half load
● THDi < 3% (linear load)
● THDi < 5% (non-linear load)
Remarks:
1. The preceding specifications are met when the mains input and bypass
input share a power source.
2. The input THDu is less than 1%.
OVC II
Specifications
Three-phase, four-wire, and PE
380 V AC/400 V AC/415 V AC (line voltage)
50/60 Hz
±6 Hz (adjustable, 0.5–6 Hz, ±2 Hz by default)
The mains input and bypass input can share a power source or use
different power sources.
OVC II
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Technical Specifications
56