UPS5000-A-(200 kVA-800 kVA)
User Manual
7.6 Bypass Input Electrical Specifications
Item
Input system
Rated input voltage
Rated frequency
Input frequency
Input system
7.7 Battery Specifications
Item
Number of
batteries
Battery
management
Cold start
Battery string
sharing
Charge voltage
7.8 Output Electrical Specifications
Item
Output system
Issue 05 (2020-04-27)
Specifications
12 V batteries, 30–44 batteries (40 by default)
NOTE
If there are 36–44 batteries, output power is not derated. If there
are 34 batteries, output power is derated to 90%. If there are 32 or
30 batteries, output power is derated to 80%.
Intelligent battery management
In the case of a mains failure, batteries can start the UPS to
power loads.
Battery string sharing is supported in a parallel system. No
battery string is shared by default.
● Equalized voltage: 2.3–2.4 V/cell, default: 2.35 V/cell (30–
42 batteries)
● Equalized voltage: 2.3–2.35 V/cell, default: 2.35 V/cell (44
batteries)
● Float voltage: 2.23–2.30 V/cell; default: 2.25 V/cell (30–
44 batteries)
Specifications
Three-phase, four-wire, and PE
Copyright © Huawei Digital Power Technologies Co., Ltd.
Specifications
Three-phase, four-wire, and PE
380 V AC, 400 V AC, or 415 V AC (line voltage)
50/60 Hz
50/60 Hz ±6 Hz (adjustable with the tolerance of
0.5–6 Hz, ±2 Hz by default).
The mains input and bypass input can share a power
source or use different power sources.
7 Technical Specifications
249