9.5 Mains Input Electrical Specifications

Item
Input system
Rated input voltage
Input voltage
Rated frequency
Input frequency
Input PF
THDi
Overvoltage category
Issue 17 (2023-07-10)
Specifications
EN 62040-2
IEC 62040-2
IEC 61000-2-2
IEC 61000-4-2
IEC 61000-4-4
IEC 61000-4-5
EN 61000-4-3
EN 61000-4-6
IEC 61000-4-8
Specifications
Three-phase, four-wire, and PE. If current is allowed in
the PE wire, input without the N wire is supported.
380 V AC, 400 V AC, or 415 V AC (line voltage)
● 80–280 V AC (phase voltage)
● At 40°C: The UPS works at full load when the voltage
● At 30°C: The UPS works at full load when the voltage
50 Hz/60 Hz
40–70 Hz
● > 0.99 (full load)
● > 0.98 (half load)
● THDi ≤ 3% (full linear load)
● THDi ≤ 5% (full non-linear load)
OVC II
Copyright © Huawei Digital Power Technologies Co., Ltd.
is 187–280 V AC and is derated to 40% load when
the voltage is 187–80 V AC.
is 176–280 V AC and is derated to 40% load when
the voltage is 176–80 V AC.