UPSJZ-T-(1 kVA–3 kVA)
User Manual
Environmental
Specifications
Relative humidity
Altitude
Storage and
transportation
temperature
Noise
IP rating

9.3 Mains Input Electrical Specifications

Table 9-3 Mains input electrical specifications
Specifications
Input power cable
Rated input voltage
Input voltage
range
2022-08-15
1 kVA
0%–95% RH (non-condensing)
● 0–2000 m: The power is not derated.
● 2000–4000 m: The power is derated by 1% for each
additional 100 m.
● > 4000 m: The UPS cannot work properly.
–40°C to +70°C (battery pack: –20°C to +40°C)
< 50 dBA@1 m (test conditions: 1 m away from any
obstacles around)
IP20
1 kVA
1 Ph (L/N) + PE, single-phase input
200 V AC/208 V AC/220 V AC/230 V AC/240 V
AC
Minimum
● Ambient temperature 0–35°C:
conversion
160 V AC/140 V AC/120 V AC/110 V AC±5%
voltage
(depend on the load rate 100%–80%/80%–
70%/70%–60%/60%–0)
● Ambient temperature 35–40°C:
175 V AC/155 V AC/135 V AC/125 V AC±5%
(depend on the load rate 100%–80%/80%–
70%/70%–60%/60%–0)
Minimum
● Ambient temperature 0–35°C:
recovery
175 V AC/155 V AC/135 V AC/125 V AC±5%
voltage
(depend on the load rate 100%–80%/80%–
70%/70%–60%/60%–0)
● Ambient temperature 35–40°C:
190 V AC/170 V AC/150 V AC/140 V AC±5%
(depend on the load rate: 100%–80%/80%–
70%/70%–60%/60%–0)
Maximum
● 300 V AC±5% (load rate: less than 80%)
conversion
● 280 V AC±5% (load rate: 80%–100%;
voltage
transfer to battery mode after 15 minutes)
9 Technical Specifications
2 kVA
2 kVA
3 kVA
3 kVA
93