Mains Input Electrical Specifications - Huawei UPS5000-A-30KTTL User Manual

Hide thumbs Also See for UPS5000-A-30KTTL:
Table of Contents

Advertisement

UPS5000-A-(30 kVA-120 kVA)
User Manual
Item
Conducted susceptibility
(CS)
Radiated susceptibility
(RS)
Electrical fast transient
(EFT)
Surge
Power magnetic
susceptibility (PMS)
Voltage dips and short
interruptions
Inrush current

3.5 Mains Input Electrical Specifications

Item
Input system
Rated input
voltage
Input voltage
Issue 17 (2024-02-21)
Standard
EN 61000-4-6
EN/IEC 62040-2
IEC 61000-4-6
EN 61000-4-3
EN/IEC 62040-2
IEC 61000-4-3
EN/IEC 62040-2
IEC 61000-4-4
EN/IEC 62040-2
IEC 61000-4-5
IEC 61000-4-8
IEC 61000-4-11
2 kA. Standard products do not have surge protection modules.
Specifications
Three-phase, four-wire, and PE
380/400/415 V AC (line voltage)
80–280 V AC (phase voltage)
● UPS5000-A-30KTTL/UPS5000-A-40KTTL/UPS5000-A-80KTTL:
0–40°C: not derated at 176–280 V AC; derated to 40% load at 176–80 V
AC
● UPS5000-A-60KTTL-H/UPS5000-A-120KTTL-H:
– 30–40°C: not derated at 198–280 V AC; derated to 35% load at 198–80
V AC
– 0–30°C: not derated at 187–280 V AC; derated to 35% load at 187–80
V AC
● UPS5000-A-60KTTL/UPS5000-A-120KTTL:
– 30–40°C: not derated at 187–280 V AC; derated to 40% load at 187–80
V AC
– 0–30°C: not derated at 176–280 V AC; derated to 40% load at 176–80
V AC
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Technical Specifications
55

Advertisement

Table of Contents
loading

Table of Contents