Initial Startup - Huawei UPS5000-H-800 kVA-NTN Quick Manual

Table of Contents

Advertisement

UPS5000-H-800 kVA-NTN
Quick Guide (480 V, 100 kVA Power Modules)

2.1.2 Initial Startup

If the equipment is started for the first time, obtain authorization for the
equipment and set related parameters on the Settings Wizard screen. If the
equipment is not started for the first time, skip this section.
Procedure
Step 1 Enter the startup password obtained through the app on the service authorization
page to complete device authorization.
Technical support engineers can obtain the service authorization code through the
app. For details, see the
Step 2 Set the language, time and date, iManager-M service, network parameters, system
parameters, and battery parameters on the Settings Wizard screen.
Set system parameters with caution. Incorrect setting may affect the normal UPS
operation.
● Set Single/Parallel after double check. Incorrect settings may affect the normal
● Output voltage level refers to the line voltage level. Set it based on site
● Set Output frequency correctly. Otherwise, loads may be affected and the UPS
● Set all battery parameters correctly based on site requirements. Battery
Issue 01 (2023-03-20)
NO TICE
NO TICE
NO TICE
UPS operation.
requirements.
may not work properly.
parameter settings are critical to battery maintenance, battery lifespan, and
UPS discharge time.