Description of Operation
Open WAGOframe in "Expert mode".
2.
3.
Next make sure that the "Device catalog" dialog window is shown on the
right-hand side of the screen. This must be activated under Device catalog
on the View menu.
Click on [Update] in the "Device catalog" dialog window.
Open a new project using New on the File menu.
4.
5.
Make sure that the "Network view" dialog window is shown on the left-
hand side of the screen. This must be activated under Network view on the
View menu. Now move the mouse to Network in the tree structure and
click on Add... in the context menu (right mouse button).
Select the device type name for your PROFIBUS master in the dialog which
opens and confirm the selection by clicking [OK].
The name of your PROFIBUS master will now be added in the tree
structure.
6.
Move the mouse to the device type name of your PROFIBUS master in the
tree structure and select it by clicking with the left mouse button.
Next go to the Device menu and click Offline parameterization.
On the FDL parameters tab of the dialog window which opens enter the
baud rate: "12 MBaud" and click on Set default values.
Confirm your entries by clicking [OK].
7.
Click Set up connection on the Device menu. The device type name of
your PROFIBUS master will now be changed to italics in the tree structure.
8.
Move the mouse to the device type name of your PROFIBUS master in the
tree structure and click on Add... in the context menu (right mouse button).
Select "0750-0333 PROFIBUS/HART Gateway" in the dialog which opens
and confirm the selection by clicking [OK].
The entry for the PROFIBUS/HART communications DTM will now be
added in the tree structure.
9.
Move the mouse once again to the device type name of your PROFIBUS
master in the tree structure and select it by clicking with the left mouse
button.
Next go to More functions on the Device menu and click on Device list on
the sub-menu.
A dialog window with a list of devices will open.