Wiring Tables and I nformation
Wire Gauge
(AWG)
22
20
18
16
14
12
Note: Maximum loop resistance should not exceed 100 Ohms.
ain board NACs are rated for 1.7 amps each. The SGM-1004A NACs are rated for 1.7 amps each.
M
Total Signal
Load
Amperes
0.06
0.12
0.30
0.60
0.90
1.20
1.50
1.7
Note: Maximum voltage drop should not exceed 3.3 Volts for Class A and 3.7 Volts for Class B.
Table 10: Wiring Table for Initiating Circuits.
Maximum Wiring Run to Last Device ( ELR)
ft.
2990
4760
7560
12000
19000
30400
Table 11: Wiring Table for NACs
Maximum Wiring Run to Last Device ( ELR)
18AWG
16AWG
ft.
m
ft.
2350
716
3750
1143
1180
360
1850
470
143
750
235
71
375
156
47
250
118
36
185
94
29
150
78
24
125
14AWG
m
ft.
m
6000
1829
8500
567
3000
915
4250
229
1200
366
1900
114
600
183
850
76
400
122
570
56
300
91
425
46
240
73
343
38
200
61
285
TM
FleX-Net
Installation and Operation Manual
m
910
1450
2300
3600
5800
9200
Max Loop
Resistance
12AWG
0hms
ft.
m
Ohms
2591
30
1296
15
579
6
259
3
174
2
129
1.5
105
1.2
87
1.0
59