installation
Vertical Terminations - Rigid/Flex Pipe 127mm x 203mm
•
Two 45
elbows equal to one 90
o
•
Vent must be supported at offsets.
•
Minimum distance between elbows is 0.3 m.
•
Maintain clearances to combustibles as listed in the "Clearances" section.
•
Horizontal vent must be supported every 0.9 m.
•
Firestops are required at each floor level and whenever passing through a wall.
•
Must use optional rigid pipe adaptor (Part# 770-994 when using rigid pipe vent systems)
Vertical Venting with Three (3) 90
One 90
elbow = Two 45
elbows.
o
o
Option
V
H + H1
A)
0.3 m Min. 0.6 m Max. 0.9 m Min.
B)
0.6 m Min. 0.9 m Max. 1.2 m Min.
C)
0.9 m Min. 1.2 m Max. 1.8 m Min.
D)
1.2 m Min. 1.5 m Max. 2.1 m Min.
E)
1.5 m Min. 1.8 m Max. 2.4 m Min.
F)
1.8 m Min. 2.1 m Max. 2.7 m Min.
G)
2.1 m Min. 2.4 m Max.
Lengths do not include elbow indicated
Restrictor Set 0 - Factory Setting
| City Series ACV60E
48
elbow. Maximum of six 45
elbows allowed.
o
o
Elbows
o
V + V1
With these
options, max
total pipe length
is 9.1 m with
max 2.4 m total
horizontal.
Please note
min. 0.3m
3 m Min.
between 90
elbows is
required.
V1
H1
o
V
H