installation
Venting Arrangement for Vertical Terminations With Straight Vertical Venting and or With a Max.
of two 90
Elbows (1 - 90
o
The shaded area in the diagram shows all allowable combinations
of straight vertical and offset to vertical terminations, using two
90
elbows, with Rigid/Flex Pipe Venting Systems.
o
•
Two 45
elbows equal to one 90
o
•
Vent must be supported at offsets.
•
Minimum distance between elbows is 0.3 m.
•
Maintain clearances to combustibles as listed in the
"Clearances" section.
•
Horizontal vent must be supported every 0.9 m.
•
Firestops are required at each floor level and whenever
passing through a wall.
•
Must use optional rigid pipe adaptor (Part# 770-994) when
using rigid pipe vent systems.
•
Refer to the "Vent Restrictor Position" section for details on
how to change the vent restrictor from the factory setting
of Set 0 through to Set 3 if required.
| City Series ACV60E
52
2 - 45
)
o =
o
elbow.
o
Horizontal (meters)
0
0.5
1.0
11
10.6
9.6
9.1
Vent Restrictor on Set 3
8.5
7.9
7.2
6.7
6.0
Vent Restrictor on Set 1
5.4
4.9
4.2
3.6
3.0
2.4
1.8
1.2
0.6
Minimum length of pipe
between elbows 0.3 m
1.5
2.0
2.5
3.6
Factory Set no Restrictor