Elbows (1 - 90 ) - Regency Fireplace Products City ACV60E Owners & Installation Manual

Table of Contents

Advertisement

installation
Venting Arrangement for Vertical Terminations With Straight Vertical Venting and or With a Max.
of two 90
Elbows (1 - 90
o
The shaded area in the diagram shows all allowable combinations
of straight vertical and offset to vertical terminations, using two
90
elbows, with Rigid/Flex Pipe Venting Systems.
o
Two 45
elbows equal to one 90
o
Vent must be supported at offsets.
Minimum distance between elbows is 0.3 m.
Maintain clearances to combustibles as listed in the
"Clearances" section.
Horizontal vent must be supported every 0.9 m.
Firestops are required at each floor level and whenever
passing through a wall.
Must use optional rigid pipe adaptor (Part# 770-994) when
using rigid pipe vent systems.
Refer to the "Vent Restrictor Position" section for details on
how to change the vent restrictor from the factory setting
of Set 0 through to Set 3 if required.
| City Series ACV60E
52
2 - 45
)
o =
o
elbow.
o
Horizontal (meters)
0
0.5
1.0
11
10.6
9.6
9.1
Vent Restrictor on Set 3
8.5
7.9
7.2
6.7
6.0
Vent Restrictor on Set 1
5.4
4.9
4.2
3.6
3.0
2.4
1.8
1.2
0.6
Minimum length of pipe
between elbows 0.3 m
1.5
2.0
2.5
3.6
Factory Set no Restrictor