Venting Introduction; Venting Arrangement For Horizontal Terminations - Regency Fireplace Products City ACV60E Owners & Installation Manual

Table of Contents

Advertisement

installation

Venting Introduction

Venting Introduction
The ACV60E uses the "balanced flue" technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer liner draws
The ACV60E uses the "balanced flue" technology co-axial system. The inner liner vents products of combustion to the outside while the outer liner draws
outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
outside combustion air into the combustion chamber, thereby eliminating the need to use heated room air for combustion and losing warm room air up the
Note: These flue pipes must not be connected to any other appliance.
chimney.
Note: These flue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or
gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or
gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.

Venting Arrangement for Horizontal Terminations

Venting Arrangement for Horizontal Terminations
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90
Note: Must use rigid pipe adapter (Part# 770-994) when using Rigid Pipe Venting Systems)
Note: Must use rigid pipe adapter (Part# 770-994) when using Rigid Pipe Venting Systems)
5.5
5.2
4.9
4.2
3.6
3
2.4
1.8
1.2
0.6
VENT RESTRICTOR SETTING:
Vent restrictor factory set at Set 0.
Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 0 to Set 2 if required.
VENT RESTRICTOR SETTING:
Note: For horizontal terminations the Regency Direct Vent Flex System may be used for installations with a maximum continuous
Vent restrictor factory set at Set 0.
Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 0 to Set 2 if required.
vent length of up to 3 meters. If longer runs are required, rigid pipe must be used.
Maintain clearances to combustibles as listed in "Clearances" section
Note: For horizontal terminations the Regency Direct Vent Flex System may be used for installations with a maximum continuous
Horizontal vent must be supported every 0.9 meters.
vent length of up to 3 meters. If longer runs are required, rigid pipe must be used.
Firestops are required at each floor level and whenever passing through a wall.
Maintain clearances to combustibles as listed in "Clearances" section
A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
Horizontal vent must be supported every 0.9 meters.
Firestops are required at each floor level and whenever passing through a wall.
A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
| City Series ACV60E
40
0.6
0.9
2
1
1478 mm
o
Horizontal (meters)
3
4
*Unit is not exactly as shown.
*Unit is not exactly as shown.
installation
(two 45
o
elbows equal one 90
o
elbow).
o
elbow (two 45
o
elbows equal one 90
5
6
*Unit is not exactly as shown.
City Series ACV60E | 43
o
elbow).