Rigid Pipe Venting Arrangements - Vertical Terminations - Regency Fireplace Products Excalibur P90EX Owners & Installation Manual

Zero clearance direct vent gas fireplace
Table of Contents

Advertisement

Rigid/Flex Pipe Venting Arrangements -
Vertical Terminations
The shaded area in the diagram shows all allowable combinations of
straight vertical and offset to vertical terminations, using two 90
with rigid pipe vent systems for Propane and Natural Gas.
Vent must be supported at offsets.
Firestops are required at each floor level and whenever
passing through a wall.
Maintain clearances to combustibles.
Note: Must use optional rigid pipe adaptor when using
rigid vent systems (Part # 510-994).
The P90EX is approved for a maximum 40 ft. straight vertical, with rigid
pipe 4" x 6-5/8" vent systems for Propane and Natural Gas, as per diagram.
The shaded area in the diagram show all allowable combinations of
straight vertical and offset to vertical terminations with rigid pipe vent
elbow,
o
systems for Propane and Natural Gas. Maximum two 45
Vent must be supported at offsets
Firestops are required at each floor level and whenever
passing through a wall.
Maintain clearances to combustibles as listed in the
"Clearances" section.
Regency Excalibur
installation
elbows allowed.
o
Please note that all vertical
measurements are taken
from the base of the unit
excluding risers or bottom
standoffs.
P90EX Direct Vent Gas Stove |
®
33