Î Press INIT key.
Î After the initialization has been successfully completed:
Check the direction of action (Code 7) and, if necessary, change it.
7.5.3
MAN – Initialization based on a manually selected OPEN
position
Before starting initialization, move the control valve manually to the OPEN position. Turn the
rotary pushbutton (
cally increasing signal pressure. The positioner calculates the differential travel/angle from
the OPEN and CLOSED positions and adopts it as the operating range with limits of lower
travel/angle range value (Code 8) and upper travel/angle range value (Code 9).
Enable configuration:
Configuration is locked again if no settings are entered within 120 seconds.
1. Turn
until Code 3 appears (reading:
No).
2. Press
, the code number 3 blinks.
3. Turn
until YES appears.
4. Press
to confirm (reading: ).
Enter the pin position:
1. Turn
until Code 4 appears.
2. Press
, the code number 4 blinks.
3. Turn
to select pin position on lever (see
relevant section on attachment).
4. Press
to confirm.
EB 8384-4 EN
) clockwise in small steps. The valve must be moved with a monotoni-
Start-up and configuration
Enable configuration
Default: No
Pin position
Default: No
mm
7-11