Code
Parameter – Readings/
no.
values [default setting]
43
Firmware info control
44
y info
[0] to 100 %, 0P, MAX, –
– –
45
Solenoid valve info
YES, HIGH/LOW, No
46* Bus address
ESC
47* Write protection PA
YES, [No], ESC
48*
Diagnostic parameters u EB 8389
49*
EB 8384-4 EN
Description
Read only
Indicates the positioner type and current firmware version in alter-
nating sequence.
Read only
Indicates the control signal y in % in relation to the travel range de-
termined during initialization.
MAX:
The positioner builds up its maximum output pressure,
see description in Code 14 and 15.
0P:
The positioner vents completely, see description in
Code 14 and 15.
– – –:
The positioner is not initialized.
Read only
Indicates whether a solenoid valve is installed or not.
If a voltage supply is connected at the terminals of the installed
solenoid valve, YES and HIGH appear on the display in alternating
sequence. If a voltage supply is not connected (actuator vented, fail-
safe position indicated on the display by the S icon), YES and LOW
appear on the display in alternating sequence.
Bus address
When write protection is active, device data can be read using PA
communication but not overwritten.
Annex A (configuration instructions)
16-7