Annex A (configuration instructions)
Operational errors
Error codes –
Recommended action
57 Control loop
Status
classification
Recommended
action
58 Zero point
Status
classification
Recommended
action
59 Auto-correction
Status
classification
Recommended
action
60 Fatal error
Status
classification
Recommended
action
16-10
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
Control loop error, the valve no longer follows the controlled variable within
tolerable times (tolerance band alarm Code 19).
• Actuator blocked
• Positioner attachment shifted subsequently
• Supply pressure no longer suffices.
[Maintenance required]
Check attachment.
Zero point incorrect
Error can occur when the positioner's attachment position is shifted or when
the valve trim is worn, particularly with soft-sealed plugs.
[Maintenance required]
Check valve and attachment of the positioner. If OK, perform a zero
calibration over Code 6 (see section 7.7).
We recommend to re-initialize the positioner if zero deviates by more than 5
%.
Errors in the positioner's data section are detected detected by automatic
monitoring and corrected automatically.
[No message]
Automatic
Error in safety-relevant data that cannot be corrected automatically. Possible
cause: EMC disturbances.
The valve is moved to fail-safe position.
Maintenance alarm (cannot be classified)
Reset over Code 36. Re-initialize the positioner.