Annex A (configuration instructions)
Code
Parameter – Readings/
no.
values [default setting]
24* LV total valve travel
1000 to 99 · 10
[1.000000], ESC
Exponential reading from
9999 travel cycles on-
wards
34* Closing direction
CL, [CCL], ESC
35* Blocking position
[0.0] mm/° /%, ESC
36* Reset
[----], Std, diAG, ESC
38* Inductive alarm
[No], YES, ESC
39
Set point deviation e info
–99.9 to 99.9 %
40
Transit time Open info
[0] to 240 s
41
Transit time Closed info
[0] to 240 s
42
Auto-w/manual-w info
0.0 to 100.0 % of the
span
16-6
Description
Limit value of total valve travel. If the limit is exceeded, the error
message and the
7
pear.
CL:
Clockwise
CCL:
Counterclockwise
Direction of rotation to reach the valve's CLOSED position (view onto
rotary switch with positioner cover open).
Needs only be entered in SUb initialization mode (Code 6).
Enter the blocking position (distance to CLOSED position)
Only necessary with SUb initialization mode.
Std:
Resets all parameters and diagnosis data to their default
settings. After a reset, the positioner must be re-initialized.
diAG: Resets diagnosis data only. Plotted reference graphs and
logs remain saved.
The positioner does not need to be re-initialized.
Indicates whether the inductive limit switch option is installed or not.
Read only
Indicates the deviation from the target position.
Read only
Minimum opening time determined during initialization.
Read only
Minimum closing time determined during initialization.
Read only
Auto mode:
Man mode:
icon corresponding to the condensed state ap-
Indicates the applied automatic set point.
Indicates the applied manual set point.
EB 8384-4 EN