Data errors
Error codes – Recommended
action
68
Control parameters
Status classification
Recommended action Confirm error, perform a reset and re-initialize the positioner.
69
Potentiometer
parameters
Status classification
Recommended action Confirm error, perform a reset and re-initialize the positioner.
70
Calibration
Status classification
Recommended action Return device to SAMSON for repair.
71
General
parameters
Status classification
Recommended action Confirm error. Check and, if necessary, change the settings of the
73
Internal device
error 1
Status classification
Recommended action Return device to SAMSON for repair.
74
PA parameters
Status classification
Recommended action Confirm error and perform a reset.
EB 8384-4 EN
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
Error in control parameters.
[Maintenance required]
Error in digital potentiometer parameters
[Maintenance required]
Error in data from production calibration. The positioner continues
operation with cold start values.
[Maintenance required]
Error in parameters not critical to control operation.
[Maintenance required]
required parameters.
Internal device error
[Maintenance required]
Error in parameters not critical to control operation.
[Maintenance required]