Samson 3730 Series Mounting And Operating Instructions page 67

Electropneumatic positioner
Table of Contents

Advertisement

2. Screw the position sensor (20) onto the
bracket (21).
The standard attached M lever with the fol-
lower pin (2) at position 35 is designed for
120 to 350 cm² actuators with 15 mm rated
travel. For other actuator sizes or travels, se-
lect the lever and pin position from the travel
table on page 5-5. L and XL levers are in-
cluded in the mounting kit.
3. Place the lever (1) and disk spring (1.2)
on the sensor shaft. Place the lever in
mid-position and hold it in place. Screw
on the nut (1.1).
20
21
1.1, 1.2
2
Fig. 5-25: Mounting according to IEC 60534-6 (NAMUR)
EB 8384-4 EN
14.1
3 14
9.1
4. Screw the two bolts (14) to the bracket
(9.1) of the stem connector (9), place the
follower plate (3) on top and use the
screws (14.1) for fastening.
5. Place the bracket with the sensor at the
NAMUR rib in such a manner that the
follower pin (2) rests in the slot of the fol-
lower plate (3), then screw the bracket
using its fixing screws onto the valve.
9
Installation
1
Lever
1.1
Nut
1.2
Disk spring
2
Follower pin
3
Follower plate
9
Stem connector
9.1
Bracket
14
Bolt
14.1
Screws
20
Position sensor
21
Bracket
5-33

Advertisement

Table of Contents
loading

This manual is also suitable for:

3730-43730-413730-453730-48

Table of Contents