Start-up and configuration
Note
The maximum possible travel must always be greater than the rated travel entered. If this is
not the case, initialization is automatically canceled (error message Code 52) because the
rated travel could not be achieved.
Enable configuration:
Configuration is locked again if no settings are entered within 120 seconds.
1. Turn
until Code 3 appears (reading:
No).
2. Press
, the code number 3 blinks.
3. Turn
until YES appears.
4. Press
to confirm (reading: ).
Enter the pin position and nominal range:
1. Turn
until Code 4 appears.
2. Press
, the code number 4 blinks.
3. Turn
to select pin position on lever (see
relevant section on attachment).
4. Press
to confirm.
5. Turn
until Code 5 appears.
6. Press
, the code number 5 blinks.
7. Turn
and set rated travel of the valve.
8. Press
to confirm.
Select the initialization mode:
1. Turn
until Code 6 appears.
2. Press
, the code number 6 blinks.
3. Turn
until NOM appears.
4. Press
to confirm the NOM initialization
mode.
7-10
Enable configuration
Default: No
Pin position
Default: No
mm
Nominal range
(locked when Code 4 =
No)
mm
Init mode
Default: MAX
EB 8384-4 EN