Samson 3730 Series Mounting And Operating Instructions page 191

Electropneumatic positioner
Table of Contents

Advertisement

Hardware errors
Error codes –
Recommended action
62 x signal
Status
classification
Recommended
action
64 i/p converter (y)
Status
classification
Recommended
action
EB 8384-4 EN
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
Actuator's measured value recording failed.
The conductive plastic element is defective.
The device continues functioning in emergency mode but it must be replaced
as quickly as possible.
The emergency mode on the display is indicated by a blinking closed-loop
operation icon and 4 dashes instead of the position reading.
Note on the open-loop operation: If the measuring system has failed, the
positioner is still in a reliable state. The positioner switches to emergency
mode where the position cannot be accurately controlled anymore. However,
the positioner continues operation according to its set point so that the process
remains in a safe state.
[Maintenance demanded]
Return device to SAMSON for repair.
Current circuit of i/p converter interrupted.
Maintenance alarm (cannot be classified)
Cannot be remedied. Return device to SAMSON for repair.
Annex A (configuration instructions)
16-11

Advertisement

Table of Contents
loading

This manual is also suitable for:

3730-43730-413730-453730-48

Table of Contents