Start-up and configuration
Select the initialization mode:
1. Turn
until Code 6 appears.
2. Press
, the code number 6 blinks.
3. Turn
until SUb appears.
4. Press
to confirm the SUb initialization
mode.
Enter the direction of action:
1. Turn
until Code 7 appears.
2. Press
, the code number 7 blinks.
3. Turn
to select the direction of action
(ää/äæ).
4. Press
to confirm.
Deactivate travel limit:
1. Turn
until Code 11 appears.
2. Press
, the code number 11 blinks.
3. Turn
until No appears.
4. Press
to deactivate the travel limit func-
tion.
Change pressure limit and control parameters:
Note
Do not change the pressure limit (Code 16). Only change the control parameters K
17) and T
(Code 18) if the settings of the replaced positioner are known.
V
7-14
Init mode
Default: MAX
Direction of action
Default: 
Travel limitation