Operation
Operating modes
(manual mode)
−
The positioner follows the manual set
point (Code 1) instead of the set point of
the process control system.
blinks: The positioner is not initialized.
Operation only possible over manual set
point (Code 1).
−
(automatic mode)
The positioner is in closed-loop operation
and follows the set point of the process
control system.
− S SAFE
The positioner vents the output. The valve
moves to the mechanical fail-safe posi-
tion.
Bar graph
In manual
and automatic
bars indicate the set point deviation that de-
pends on the sign (+/–) and the value. One
bar element appears per 1 % set point devi-
ation.
If the positioner has not been initialized, (
blinks on the display), the bar graph indi-
cates the lever position in degrees in relation
to the mid-axis. One bar element corre-
sponds to approximately a 5° angle of rota-
tion. The fifth bar element blinks (reading >
30°) if the permissible angle of rotation has
been exceeded. Lever and pin position must
be checked.
6-2
Status messages
−
−
−
These icons indicate that an error has oc-
curred.
A classified status can be assigned to each
error. Classifications include "No message",
"Maintenance required", "Maintenance de-
manded" and "Maintenance alarm" (see
u EB 8389-1 on EXPERTplus valve diagnos-
tics).
This indicates that the codes marked with an
asterisk (*) in the code list are enabled for
configuration (see the 'Start-up and configu-
ration' section).
modes, the
Maintenance alarm
Maintenance demanded/Mainte-
nance required
blinks: Out of specification
Enable configuration
EB 8384-4 EN