Samson 3730 Series Mounting And Operating Instructions page 192

Electropneumatic positioner
Table of Contents

Advertisement

Annex A (configuration instructions)
Error appendix
Error codes – Recommended
action
65
Hardware
Status classification
Recommended action Confirm error and return to automatic mode or perform a reset and
66
Data memory
Status classification
Recommended action Return device to SAMSON for repair.
67
Check calculation
Status classification
Recommended action Confirm error. If this is not possible, return the device to SAMSON for
16-12
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
Initialization key jammed
A hardware error has occurred. The positioner changes to the fail-safe
position (SAFE).
Maintenance alarm (cannot be classified)
re-initialize the positioner. In the problem still persists, return device to
SAMSON for repair.
No more data can be written to the memory, e.g. because written data
deviate from read data. The valve moves to the fail-safe position.
Maintenance alarm (cannot be classified)
Hardware controller monitored by test calculation.
Maintenance alarm (cannot be classified)
repair.
EB 8384-4 EN