Samson 3730 Series Mounting And Operating Instructions page 103

Electropneumatic positioner
Table of Contents

Advertisement

by means of a pressure signal which is routed to the actuator externally. The blocking posi-
tion ensures that the plant continues to operate with this valve position.
By entering the blocking position (Code 35), closing direction (Code 34), pin position (Code
4), nominal range (Code 5) and direction of action (Code 7), the positioner can calculate the
positioner configuration.
Î Perform a reset before re-initializing the positioner if the substitute positioner has already
been initialized (see the 'Operation' section).
Enable configuration:
Configuration is locked again if no settings are entered within 120 seconds.
1. Turn
until Code 3 appears (reading:
No).
2. Press
, the code number 3 blinks.
3. Turn
until YES appears.
4. Press
to confirm (reading: ).
Enter the pin position and nominal range:
1. Turn
until Code 4 appears.
2. Press
, the code number 4 blinks.
3. Turn
to select pin position on lever (see
relevant section on attachment).
4. Press
to confirm.
5. Turn
until Code 5 appears.
6. Press
, the code number 5 blinks.
7. Turn
and set rated travel of the valve.
8. Press
to confirm.
EB 8384-4 EN
Start-up and configuration
Enable configuration
Default: No
Pin position
Default: No
mm
Nominal range
(locked when Code 4 =
No)
mm
7-13

Advertisement

Table of Contents
loading

This manual is also suitable for:

3730-43730-413730-453730-48