Samson 3730 Series Mounting And Operating Instructions page 189

Electropneumatic positioner
Table of Contents

Advertisement

Error codes –
Recommended action
53 Initialization time
exceeded
(Init time >)
Status
classification
Recommended
action
54 Initialization –
solenoid valve
Status
classification
Recommended
action
55 Transit time too
short
(transit time <)
Status
classification
Recommended
action
56 Pin position
Status
classification
Recommended
action
EB 8384-4 EN
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
Initialization takes too long. The positioner returns to the previous operating
mode.
• No pressure in supply line or pneumatic leakage
• Supply air failure during initialization
[Maintenance required]
Check attachment and supply air line. Re-initialize the positioner.
A solenoid valve is installed (Code 45 = YES) and has not been connected
1)
or not properly. As a result, actuator pressure cannot build up. The alarm
is generated when you attempt to initialize the positioner.
If you attempt to initialize the positioner from the fail-safe position (SAFE).
2)
[Maintenance required]
Check connection and supply voltage of the solenoid valve (Code 45
1)
High/Low).
Set the MAN mode in Code 0. Re-initialize the positioner.
2)
Actuator transit times detected during initialization are so short that optimal
positioner tuning is impossible.
[Maintenance required]
Check the volume restriction setting as described in section 7.2. Re-initialize
the positioner.
Initialization canceled because selected NOM and SUB initialization modes
require the pin position to be entered.
[Maintenance required]
Enter pin position over Code 4 and rated travel/angle over Code 5. Re-
initialize the positioner.