® Nominal travel/angle
Press
.
Select the initialization mode:
® Code 6
Turn
Press
, Code 6 blinks
Turn
® NOM
to confirm the NOM as the initial-
Press
ization mode.
Start initialization:
4
Press INIT key to start initialization!
Note: After initialization, check the direction
of action and, if necessary, change it
(Code 7).
7.6.3 MAN – Initialization based
on a manually selected
range
Before starting initialization, move the con-
trol valve manually to the OPEN position by
turning
in small steps. The valve must
move to the required valve position with a
monotonically increasing signal pressure.
The positioner calculates the differential
travel/angle using the OPEN and CLOSED
positions and adopts it as the operating
range with limits of travel/angle range start
Initialization mode
Default MAX
(Code 8 ) and travel/angle range end
(Code 9 ).
Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
® Code 3 , display: No
Turn
Press
, Code 3 blinks
® YES
Turn
Press
, display
Enter the pin position:
mm
® Code 4
Turn
, Code 4 blinks
Press
Turn
® Pin position on lever (see rele-
vant section on attachment)
Press
. The reading of the nominal range
appears in mm/°.
Start-up – Settings
Default No
Pin position
Default No
EB 8384-5 EN
59