Maintenance Mode

5-3

Maintenance Mode

5-3-1 Maintenance Mode

5-3-2 Initialization

AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
The set values of the K3NH can be initialized and field calibration of the K3NH is
possible in maintenance mode. The operations of the K3NH in this mode are de-
scribed below.
• The K3NH will be in maintenance mode if the Mode and Shift Keys are simulta-
neously pressed while the K3NH is turned on.
• The K3NH in maintenance mode will go into RUN mode if the Escape Key is
pressed.
Press the Mode and Shift Keys
while turning the K3NH on.
Maintenance mode
Follow the steps described below to reset the set values of the K3NH to factory-
set values.
1, 2, 3...
1. Press the Mode and Shift Keys simultaneously while turning the K3NH on.
The mant maintenance mode setting will be displayed.
2. Press the Mode Key for more than one second. The re in initialization set-
ting will be displayed.
3. Press the Up Key to display no.
Power On
RUN mode
RUN mode
1 second
Setting mode
Set Value LED Display Model
Set Value LED Display Model
Set Value LED Display Model
Section 5-3
Press the Escape and Up
Keys for 1 second.
Protect mode
Basic Model
Basic Model
Basic Model
77