Maximum rated voltage: 24 VDC
Load current: 50 mA
Current leakage with transistor turned off: 100 µA.
The following figures show connections for linear output.
K3NH with Linear
Output Board,
K31-L1 or K31-L4
+
4 to 20 mA
The following linear output conditions are required.
Linear output
Permissible load
600 Ω max.
4 to 20 mA
500 Ω min.
1 to 5 V
1 mV/10 digit
1 kΩ min.
Refer to Section 6 BCD Output for the terminal arrangement and interface.
K3NH with Linear
Output Board,
K31-L2 or K31-L5
+
1 to 5 V
Resolution
resistance
4096
4096
4096
Section 2-3
K3NH with Linear
Output Board,
K31-L3 or K31-L6
+
1 mV/10 digit
Output error
±0.5% FS
±0.5% FS
±1.5% FS