Comparative Output Pattern
• The pattern of HH, H, L, LL, and PASS comparative outputs is set in the option
menu.
nomal: Standard output
=one: Zone output
leUel: Level output
Standard Output
H or HH Comparative Output:
Turns ON when the measured value is larger than the H or HH setting value.
PASS Output:
Turns ON when LL, L, H, and HH comparative outputs are all OFF.
L or LL Comparative Output:
Turns ON when the measured value is smaller than the L or LL setting value.
HH setting value
H setting value
L setting value
LL setting value
HH comparative output
H comparative output
PASS
L comparative output
LL comparative output
Setting
Measured value
Section 3-2
Default
nomal