Scaling Upper Limit Value (In H); Scaling Lower Limit Value (In L); Decimal Point Position (Dec P) - Omron K3NH Operation Manual

Temperature meter
Table of Contents

Advertisement

Setting Mode
in h
in l
dec p
FUNCTION
SETTING
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
Scaling Upper Limit Value
Scaling Lower Limit Value
Decimal Point Position
In the case of voltage or current inputs, by setting input value 1 to correspond to
the scaling lower limit value and input value 2 to correspond to scaling upper limit
value, scaling can be displayed for the line that connects these input values to-
gether.
Scaling values are displayed only for voltage or current inputs. Scaling values
cannot be displayed for thermocouple or temperature-resistance thermometer
inputs.
Scaling upper limit value
Scaling lower limit value
Scaling
Sensor voltage or current output is converted into a value within a specified
range.
For example, if a sensor with 4- to 20-mA output is connected to the K3NH and
the K3NH is set so that it will display "0" for 4-mA input and "999" for 20-mA input,
the following will be the relationship between input and display values.
Display
value
• Scaling Value
Setting
Scaling upper limit value
Scaling lower limit value
• Decimal Point Position
Setting range
%%%%
%%%.%
%%.%%
%.%%%
Display value
Input value 1
4 mA
Input value
Setting range
–1999 to 9,999
–1999 to 9,999
Default value
%%%%
Section 3-2
Input value
Input value 2
20 mA
Default value
100
0
31