Setting Mode
REFERENCE
SETTING
EXAMPLE
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
32
Refer to 5-1 Teaching Function.
Follow the steps described below to input the following.
Scaling upper limit value = "500"
Scaling lower limit value = "100"
Decimal point position = "%%%.%"
1. Press the Mode Key for more than one second while the setup setup menu
1, 2, 3...
is displayed. The in t input type setting will appear.
2. Press the Mode Key twice to display in h scaling upper limit value setting.
3. Press the Shift Key to display the present set value 100 for changing. The
PROG indicator will flash.
4. Press the Up and Shift Keys to set the value to 500. The input value will be
validated automatically if no change is made for five seconds. The in h
scaling upper limit value setting will be displayed again.
Note Press the Mode Key to enter the set value immediately. The in l
scaling lower limit value setting will be displayed for setting the next
parameter.
5. Press the Mode Key to display in l scaling lower limit value setting.