Standby Sequence
When the K3NH is tuned on, the K3NH will have no output until the measured
value is within the PASS range. This function avoids unnecessary output until
the output is within the measurement range after the power is turned ON.
Setting
ON/OFF
This setting is only available for the K3NH with the Comparative Output Units.
Follow the steps described below to set the standby sequence to ON.
1. Press the Mode Key for more than one second while the opt option menu is
1, 2, 3...
displayed. The aUg average processing setting will appear.
2. Repeatedly press the Mode Key until the stdby standby sequence setting is
displayed.
3. Press the Shift Key to display present set value off for changing. The
PROG indicator will flash.
4. Press the Up Key to set the value to on. The setting will be validated auto-
matically if no change is made for five seconds. The stdby standby se-
quence setting will be displayed again.
Note Press the Mode Key to enter the setting immediately. The next pa-
rameter will be displayed for setting.
Unit
---
Set Value LED Display Model
Set Value LED Display Model
Set Value LED Display Model
Set Value LED Display Model
Set Value LED Display Model
Section 3-2
Default
OFF
Basic Model
Basic Model
Basic Model
Basic Model
Basic Model