Setting Mode
insh
insl
FUNCTION
SETTING
SETTING
EXAMPLE
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
44
Upper-limit Compensation Value
Lower-limit Compensation Value
The upper- and lower-limit values of the sensor can be shifted. If both the upper-
and lower-limit values are shifted by 2°C each, for example, a process value of
200°C will be treated as 202°C after compensation.
Temperature
Upper-limit value
Lower-limit value
Set value
–1999 to 9,999
Follow the steps described below to set both the upper- and lower-limit compensation
values to 2.
1. Press the Mode Key for more than one second while the opt option menu is
1, 2, 3...
displayed. The aUg average processing setting will appear.
2. Press the Mode Key twice to display the insh upper-limit compensation val-
ue setting.
Upper-limit
compensation value
After compensation
Before com-
pensation
Lower-limit
compensation value
Unit
---
Set Value LED Display Model
Set Value LED Display Model
Set Value LED Display Model
Section 3-2
Input (% FS)
Default
0
Basic Model