Maintenance Mode
Calibration (0 to 10 V)
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
7. Press the Shift Key to select whether or not to accept the settings.
8. Press the Up Key to select yes.
9. Press the Mode Key to overwrite all calibration data and to put the K3NH into
RUN mode. The calibration data will not be overwritten if no is selected.
1. First, the sure alarm display will appear. This will not appear once field cal-
1, 2, 3...
ibration is performed.
2. Press the Mode Key to display 2U 10. The teaching indicator will be lit.
3. Press the RESET/TEACH Key to display the calibration value setting. Then
set the output of STV to 10 V. The teaching indicator will flash. After the value
stabilizes (i.e., the fluctuation of the value is less than several digits), press
the Mode Key to tentatively register the calibration data.
4. The display will change to 2U 0 for 0-V calibration. The teaching indicator will
be lit.
Set Value LED Display Model
Set Value LED Display Model
RUN mode
Set Value LED Display Model
Set Value LED Display Model
Set Value LED Display Model
Set Value LED Display Model
Section 5-3
Basic Model
Basic Model
Basic Model
Basic Model
Basic Model
Basic Model
91