Technical data
8.3 Buffer times
8.3.2

SITOP UPS1100

Type of
power
supply
Load cur-
rent
1 A
2 A
3 A
4 A
6 A
8 A
10 A
12 A
14 A
16 A
20 A
30 A
40 A
* When determining buffer times, the discharge duration of new and completely charged
battery modules at a battery temperature of 25 °C down to shutdown of the DC UPS (min.
20 V) was used as basis. Buffer times for additional values can be determined using the SITOP
Selection Tool: TIA Selection Tool (http://www.siemens.com/tst-powersupply)
With two SITOP UPS1100 battery modules connected in parallel and one DC UPS module
1)
SITOP UPS1600 40 A.
With three SITOP UPS1100 battery modules connected in parallel and one DC UPS module
2)
SITOP UPS1600 40 A.
242
6EP4131-
6EP4132-
0GB00-0AY0
0GB00-0AY0
24 V/1.2 Ah
24 V/2.5 Ah
High tem-
perature
Buffer
Buffer
times*
times*
25 min
1 h 30 min
10 min
50 min
6 min
35 min
3 min
25 min
< 1 min
15 minutes
-
10 min
-
6 min
-
5 minutes
-
4 minutes
-
3 min
-
1 minute
-
3 min, x2
1)
-
3 min, x3
2)
6EP4133-
6EP4133-
0GB00-0AY0
0JB00-0AY0
24 V/3.2 Ah
24 V/5 Ah
LiFePO4
Buffer
Buffer
times*
times*
1 hr 20 min
4 h
50 min
2 h 10 min
30 min
1 h 30 min
20 min
1 h 10 min
10 min
48 min
6 min
37 min
4 minutes
26 minutes
2 minutes
23 min
1 minute
21 min
< 1 min
18 min
-
13 min
-
17 min, x2
-
13 min, x2
Equipment Manual, 07.2021, A5E37775406-11-76
6EP4134-
6EP4135-
0GB00-0AY0
0GB00-0AY0
24 V/7 Ah
24 V/12 Ah
Buffer
Buffer
times*
times*
4 h 30 min
8 h 30 min
2 h 10 min
4 h 20 min
1 h 30 min
2 h 40 min
1 h 5 min
1 h 50 min
35 min
1 h 20 min
25 min
50 min
15 minutes
40 min
12 minutes
30 min
10 min
25 min
8 min
20 min
5 minutes
15 minutes
1 minute
6 min
1)
< 1 min
3 min
1)
SITOP UPS1600 / BAT1600 / UPS1100