Engineering and remote access
3.4 SIMATIC STEP 7 in the TIA Portal
6. Activate checkbox "Flash LED" in menu "Online & diagnostics > Functions > Assign PROFINET
device name".
7. Check at which SITOP UPS1600 in the network the "SF" LED flashes.
By checking the flashing LEDs, you can uniquely identify all SITOP UPS1600 in a network.
Note the device name and the IP address of the required SITOP UPS1600 in order to load a
configuration.
Changing the device name of the SITOP UPS1600
1. In STEP 7, in the tabular area of the Network view, select the "Network overview" table.
2. Overwrite the name in the "Device" column in the row of the PROFINET device involved.
You have changed the name of the SITOP UPS1600 device.
The name is adapted in the graphical area of the network view.
Changing the PROFINET device name of the SITOP UPS1600 via the properties of the PROFINET
interface
You can change the PROFINET device name using the properties of the PROFINET interface.
1. In the Network or Device view of the Hardware and Network editor of STEP 7, select the
PROFINET interface of a PROFINET device.
2. In the Inspector window navigate to "Ethernet addresses" in the "PROFINET" area.
3. Deactivate the "Generate automatically the PROFINET device name" checkbox.
4. Enter the new PROFINET device name in the appropriate field.