Safety and security
1.1 General safety instructions
1.1.1

SITOP BAT1600 and UPS1100

NOTICE
The maintenance, installation and commissioning may only be performed or monitored by
personnel who are familiar with batteries and the necessary precautionary measures.
Ensure that non-authorized personnel do not get involved with these batteries.
When storing, installing and operating the battery modules, the regulations of VDE 0510
Part 2 / EN 50272-2 or the applicable national regulations must be complied with.
For lead-gel batteries, it must be carefully ensured that the battery module location is
adequately ventilated.
Battery module location: In the lower part of the control cabinet or at the coolest location in
the control cabinet to optimize the battery service life.
Dimension the power cables corresponding to the fuse in the battery module.
The fuse should only be inserted in the fuse holder when commissioning the device.
The "+" and "-" power connections of the battery module may only be connected to the
UPS1600 UPS module, or when BAT1600 or UPS1100 battery modules of the same type are
connected in parallel. Do not connect the power connections with "0 V" or "Ground" of
the power supply system!
Only connect battery modules in parallel if they have the same charge state.
When replacing the batteries, always use batteries with the same batch number and
approximately the same charge state. Only the types listed in Section "Battery replacement"
should be used. The approval becomes null and void if other batteries are used.
The batteries must always be disposed of in the discharged condition according to the
applicable regulations.