Diagnostics; Alarm Monitoring - Siemens SITOP UPS1600 Equipment Manual

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Engineering and remote access
3.9 Web server
3. Click on "Download"
Firmware update starts.
A message is displayed after a successful update.
4. Carry out a manual restart at the SITOP UPS1600 by clicking on button "Reboot".
5. After the restart, the SITOP UPS1600 automatically updates the firmware.
The firmware update has been performed successfully.
3.9.6

Diagnostics

3.9.6.1

Alarm monitoring

You can use the web server to obtain information about active alarms and the history of the
alarms. Every alarm that concerns the SITOP UPS1600 and the connected battery modules is
recorded. You can display active alarms using "Diagnostics > Alarms > Pending alarms".
Pending alarms
The currently pending system alarms are provided in this list.
Displaying the alarm history
1. Select menu "Diagnostics".
2. Select the "Alarm history" entry under "Alarms" in the navigation.
The alarm history is displayed in a tabular form.
136
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76