Siemens SITOP UPS1600 Equipment Manual page 183

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Error
Ex-
Severity
Type
tend-
ed
Error
Type
257
20
MD
257
21
MR
257
22
MD
257
23
N
257
24
MD
257
26
MR
257
27
MR
257
28
N
257
29
N
257
30
N
257
31
N
257
32
N
257
33
N
257
41
MR
257
42
MD
257
43
MD
257
44
MD
257
45
MD
257
46
MD
257
47
MD
258
1
MD
258
2
MD
258
3
MR
258
4
MR
258
5
MD
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
Alarm Text
Low voltage mode
Buffering
Communication with device
failed
Device powered up
Wrong battery polarity
Insufficient charge level
Deep discharge battery
Buffer readiness disabled
Shutdown completed, ping
test successfully completed.
Charge current reduced due
to system load
Battery fully charged
Charging current reduced
manually
The charging function was
deactivated by a control
command
Battery almost discharged as
the charging function is
deactivated.
Battery parameters corrupt
(battery index: 1)
Battery parameters corrupt
(battery index: 2)
Battery parameters corrupt
(battery index: 3)
Battery parameters corrupt
(battery index: 4)
Battery parameters corrupt
(battery index: 5)
Battery parameters corrupt
(battery index: 6)
Battery defective (battery
index: {1:d})
Deep discharge battery, no
charging possible (battery
index: {1:d}).
Battery temperature high
(battery index: {1:d})
Battery temperature low
(battery index: {1:d}).
Communication with battery
fault (battery index: {1:d})
Help Text
Input voltage of UPS1600 is too low. UPS1600 is not ready for
buffering.
Device is in buffer mode.
PROFINET connection available - UPS1600 is defective
Device powered up
Wrong battery polarity - check battery connections.
The battery charge level is too low to guarantee the configured
buffer capacity.
Battery is deep discharged - no buffering possible
Buffer mode was deactivated by the bridge, rotary coding
switch or in REMOTE mode per command.
UPS1600 was successfully shut down.
Charge current was reduced due to system load
Battery is fully charged, buffer standby available
The charging current has been reduced by manual adjustment.
The charging function was deactivated by a control command
The batteries are no longer charged.
The battery is almost discharged as the charging function is
deactivated. It is recommended that the charging function is
immediately reactivated.
Battery defective - replace battery
Battery defective - replace battery
Battery defective - replace battery
Battery defective - replace battery
Battery defective - replace battery
Battery defective - replace battery
Battery defective - check fuse and battery voltages.
Battery is deep discharged - replace battery.
Battery temperature too high - battery life will be shortened
Battery temperature too low - reduced buffer current
Communication with formerly known battery is no longer pos-
sible - check communication
Troubleshooting
183