Diagnostics; Firmware Update - Siemens SITOP UPS1600 Equipment Manual

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Allocating the SITOP UPS1600 a device name (online)
In order that the configured IO controller can address the SITOP UPS1600, you must assign
each individual IO device (including SITOP UPS1600) the configured device name.
For the procedure described below, the SITOP UPS1600 and the station for the PG/PC must be
accessible online through Ethernet.
1. Open HW Config.
2. In the "Target system > Ethernet" menu, click on "Assign device name".
3. In the "Assign device name" dialog, in the "Device name" field, select SITOP UPS1600.
4. In the "Available devices" select the SITOP UPS1600. Using the "Flash" button, you can flash
the LED on the SITOP UPS1600 so that the device can be uniquely identified.
5. Click on the "Assign name" button.
After the name assignment, you can bring the IO controller into the RUN operating state.
When powering up, the IO controller distributes the configuration information to the
SITOP UPS1600 and then goes into cyclic operation.
3.5.6

Diagnostics

The following data can be fetched using the Diagnostics function:
Group
SITOP UPS1600 general
Fetching diagnostics data
You can use the "Station > Open online" menu command in "HW Config" to select the
SITOP UPS1600 and view the diagnostics data.
3.5.7

Firmware update

The SITOP UPS1600 is reset while updating the firmware. For safety reasons, the
output is switched off.
Ensure that no damage is caused to the plant or system.
Ensure that the PG/PC and/or all switches, routers and gateways that are used have an
independent power supply during the firmware update.
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
WARNING
Value
Article number
Serial number
Engineering and remote access
3.5 SIMATIC STEP 7
101