5.2

SITOP BAT1600

Installing the device in a housing or a control cabinet
The SITOP BAT1600 battery modules are built-in devices. They must be installed in a
housing or control cabinet where only qualified personnel have access.
Note
Install battery modules at the coolest location in the control cabinet (e.g. in the lower section
of the control cabinet).
For 2.5 Ah, 3.2 Ah and 7.5 Ah devices
Devices 6EP4132-0JA00-0AY0 (2.5 Ah), 6EP4133-0GA00-0AY0 (3.2 Ah) and 6EP4134-0JA00-
0AY0 (7.5 Ah) can be snapped onto a DIN rail (see Chapter Mechanical system (Page 246)).
Using a wall adapter, these modules are also suitable for wall mounting
For 12 Ah device
Device 6EP4135-0GE00-0AY0 (12 Ah) is designed for being directly mounted on a wall. 4 x
M5 screws should be used for the purpose.
Note
To improve the fire protection class, for the 3.2 Ah and 12 Ah battery modules, the accessory
pack includes a transparent fire protection cover for the fuse.
Mounting
To mount the device on a DIN rail, place the device with the DIN rail guide at the upper edge
of the rail and snap it in downwards. If this is too difficult, press slider ⑩ at the same time, as
described under "Removal".
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76