Siemens SITOP UPS1600 Equipment Manual page 132

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Engineering and remote access
3.9 Web server
• The SITOP UPS1600 has an IP address that is known to you.
• Activate access to the web server:
– SIMATIC STEP 7 in the TIA Portal, see Parameterizing the UPS1600 (Page 70).
– SIMATIC STEP 7 see Parameter assignment (Page 92).
– without SIMATIC STEP 7:
Procedure
1. Connect the client (PG, PC) via the PROFINET interface with the SITOP UPS1600 device.
2. Open the web browser.
In the address dialog box of the web browser, enter the IP address of the SITOP UPS1600 in
the form http://ww.xx.yy.zz (input example: http://192.168.0.14).
The overview page is displayed after the connection to the web server has been successfully
established. Click on the logon button to display the logon page.
3. Enter the logon information in the logon page.
Initial values:
– User name: "admin"
– Password: "admin"
On the logon page, the license information of the SITOP UPS1600 system - as well as the
current web server certificate - can be downloaded.
4. Press the enter key.
The start page of SITOP UPS1600 opens. You can navigate to further menus from the start
page.
132
Device in the state when supplied:
1. Turn both rotary coding switches into the REN and OFF positions.
2. Switch the device off and on again. Please wait approximately 1 minute as a new
certificate is created due to the IP address change.
The device can now be accessed via https://192.168.20.220.
3. Login with name "admin" and password "admin".
4. Under "HW Configuration → General → Web server → Settings", the web server must
be permanently activated ("Activate web server on this module").
5. Under "HW Configuration → General → Communication interface", IP address,
subnet mask and router address can be set.
6. By clicking on "Download to device" configuration changes are transferred to the
SITOP UPS1600 and become immediately effective. The connection to the web server
is interrupted if the IP address is changed. After regenerating the certificate, the device
can be accessed under the new IP address.
Note
For devices with software version V2.1.1, after changing the IP address, the device
must be switched off and switched on again.
If an IP address was previously configured, and if this is not known, then this can be
changed using SITOP Manager, Step 7 or PRONETA - or the device can be reset to the
original delivery state.
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76