Siemens SITOP UPS1600 Equipment Manual page 114

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Engineering and remote access
3.6 Cyclic and acyclic data
0x0006: Device information parameters (reading)
Data
HW revision
SW revision
Boot loader version
Max output current [1 A]
Fill byte(s)
MLFB/Order number
Serial number
Device name
Version number
0x0007: Hardware settings parameters (reading)
Data
Buffer time [1 s]
Buffer threshold [0.01 V]
Buffering allowed
Enable reset
Start from battery
Selected battery profile
0x0008: Buffering parameters (reading/writing)
Data
Expected buffer current [0.1 Ah]
from V2.0 and higher
0x0009: Maintenance parameters (reading/writing)
Data
Resistor test interval [1 h] from
V2.1
114
Description
Hardware version
Software release
Boot loader version
Maximum output current
-
MLFB/order number (Article number)
Serial number
Device name
Version number
Description
Buffer time: After the selected buffer time has expired, the SITOP
UPS1600 switches off the load output. The actual buffer time that
can be achieved depends on the connected loads and energy stor-
age devices.
Connection threshold: Switching voltage for buffering. Buffering is
active below this value.
Activate or deactivate buffer mode. This setting is only accepted by
the SITOP UPS1600 in the Remote Enable (REN) operating mode.
Enable reset: If, during buffer mode, the input voltage becomes
available again, then the output of the SITOP UPS1600 is switched
off for a selectable time in order to reset connected loads.
Start from battery: Setting at the signal terminal for function "Start
from battery".
Profile of the selected battery: The battery charging behavior is set
at the signal terminals. The setting is only used, if the SITOP
UPS1600 is not in the "Remote Enable" (REN) mode.
Description
Expected buffer current: Estimated average load current during
buffer mode.
Description
R test interval
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
Data type
Unsigned16
Unsigned16
Unsigned16
Unsigned8
1 x Unsigned8
VisibleString(20)
VisibleString(16)
VisibleString(30)
VisibleString(50)
Data type
Unsigned16
Unsigned16
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Data type
Unsigned16
Data type
Unsigned16