Siemens SITOP UPS1600 Equipment Manual page 41

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

States of the LEDs
LED 1 (O.K./BAT.)
Signaling
LED 2 (BAT.> 85%)
Signaling
The LED and the relay contact (see Chapter Relay outputs (Page 44)) have two meanings:
1. If no additional settings have been made, then the previous LED signaling applies.
2. If an expected buffer current and a buffer time are set under the hardware configuration,
then the LEDs and the relay contact serve as an indicator when buffering is possible with the
two parameters – or is no longer possible.
Note
From the instant in time when the SITOP UPS1600 is switched over into the buffer mode, for
the evaluation, instead of the expected buffer current, the actually measured buffer current is
used. As a consequence, the status of the LEDs and the relay can also change.
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
6EP4134-3AB00-...
6EP4136-3AB00-...
6EP4137-3AB00-...
Off
DC-UPS off
Red
DC-UPS defect (severe hardware fault)
Flashing red
Firmware update
(0.25/0.25)
Flashing red (1/1)
Software corrupted
Flashing yellow
Critical temperature identified, overtemperature or overvoltage at the input
(0.25/0.25)
Flashing yellow
Buffer mode, output off
(1/1)
Yellow
Buffer mode, output on
Flashing green
DC-UPS OK, output off
(1/1)
Green
DC-UPS OK, output on
6EP4134-3AB00-...
6EP4136-3AB00-...
6EP4137-3AB00-...
Off
Battery module charge state < 10 %
Flashing green
10 % < battery module charge state < 85 % or firmware update
(0.25/0.25)
Flashing green
85 % < battery module charge state < 100 %
(1/1)
Green
Battery module charge state = 100 %
Description, device design, dimension drawing
2.4 Operating displays and signaling
41