Engineering and remote access
3.9 Web server
Basic unit
Buffering
Parameter
Connection threshold
Buffer time
Maximum buffer time
1)
Discharge cut-off voltage at 20 °C
Additional buffer time after the PC was powered down.
Expected buffer current
1)
Reset time:
Buffering allowed
Enable reset after buffering
Parameter only available from SW version V2.0 and higher
1)
Parameter only available from SW version V2.1 and higher
2)
Valid from V2.0.4 or V2.1
3)
150
Value range
21 - 25 V
1 - 32767 s
Yes / No
18 - 23 V
1 - 300 s
3)
0 - 40 A
1 - 120 s
Yes / No
Yes / No
Equipment Manual, 07.2021, A5E37775406-11-76
Default setting
22.5 V
600 s
No
18.5 V (for LiFePO4 battery 20.5 V)
60 s
0 A
5 s
Yes
No