Meter Setting - Alpha ESS Storion-SMILE5 Installation, Operation & Maintenance Manual

Energy storage system
Table of Contents

Advertisement

Your Smart Energy
2.3.5

Meter setting

2.3.5.1 SM60A
Step 1: Click the "Enter" button to enter the menu
interface.
Step 3: You will get into the code interface. Then
click the "Shift" button to enter the address
interface.
Step 5: Click the "Enter" button to get back to the
menu interface. Then click the "Shift" button 5
times to enter the save interface.
___________________________________________________________________
Page 34
Installation
There are 3 buttons on the front of the electricity
meter:
1. Down arrow: shift button
2. Up arrow: value adjusting
3. Enter button / Menu button
Step 2: Click the "Enter" button to input the
password. The initial password is 0000. Then
click the "Enter" button.
Step 4: Please set the meter address by using the
"Value adjusting" button, the Grid meter (DC, AC
and Hybrid system) address is set to 003, and the
PV meter (AC and Hybrid system) address is set
to 004.
Step 6: Click the "Shift" button to save the setting.
Alpha ESS Co., Ltd.