Alpha ESS STORION-T50 Operation & Maintenance Manual

Alpha ESS STORION-T50 Operation & Maintenance Manual

Hide thumbs Also See for STORION-T50:

Advertisement

Quick Links

@AlphaEnergyStorageSystem
@AlphaESS
Alpha ESS Co., Ltd.
+86 513 8060 6891
info@alpha-ess.com
www.alpha-ess.com
JiuHua Road 888, High-Tech Industrial Development
Zone 226300 Nantong City, Jiangsu Province
Alpha ESS Europe GmbH
+
49 610 3459 1601
europe@alpha-ess.de
www.alpha-ess.de
Paul-Ehrlich-Straße 1a 63225 Langen
Alpha ESS Italy S.r.l.
+39 599 239 50
info@alpha-ess.it
www.alpha-ess.it
Via Loda,17-41013 Castelfranco Emilia(MO)
Alpha ESS UK Co., Ltd
uk@alpha-ess.com
Drake House, Long Street, Dursley, gl11 4hh
Alpha ESS USA, Inc.
USA@alpha-ess.com
638 S Ahwanee Ter Sunnyvale, California,
94085 United States of America
@alpha_ess
@AlphaESS
www.alpha-ess.com
Alpha ESS Suzhou Co., Ltd.
+86 512 6828 7609
info@alpha-ess.com
www.alpha-ess.com
Building 10-A, Canal Town Industrial Park,
99 Taihu E Rd, Wuzhong District, Suzhou 215000
Alpha ESS Australia Pty. Ltd.
+61 1300 968 933
australia@alpha-ess.com
www.alpha-ess.com.au
Unit 1, 2 Ralph Street Alexandria NSW 2015
Alpha ESS Korea Co., Ltd
+82 64 721 2004
korea@alpha-ess.com
2F, 19-4, Nohyeong 11-gil, Jeju-si, Jeju-do,
Republic of Korea
Alpha ESS International Pte. Ltd.
Singapore@alpha-ess.com
Blk 55 Ayer Rajah Crescent #01-01, Singapore
139949
OPERATION & MAINTENANCE MANUAL
INSTALLATIONMANUAL
OF ENERGY STORAGE SYSTEM (ESS)
ENERGYSTORAGESYSTEM(ESS)
STORION-SMILE-T10(INDOOR)
STORION-T50/T100 (INDOOR, WITH M48112-S)
V02

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the STORION-T50 and is the answer not in the manual?

Questions and answers

Summary of Contents for Alpha ESS STORION-T50

  • Page 1 INSTALLATIONMANUAL @AlphaEnergyStorageSystem @AlphaESS @alpha_ess @AlphaESS www.alpha-ess.com OF ENERGY STORAGE SYSTEM (ESS) ENERGYSTORAGESYSTEM(ESS) Alpha ESS Co., Ltd. Alpha ESS Suzhou Co., Ltd. +86 513 8060 6891 +86 512 6828 7609 STORION-SMILE-T10(INDOOR) info@alpha-ess.com info@alpha-ess.com STORION-T50/T100 (INDOOR, WITH M48112-S) www.alpha-ess.com www.alpha-ess.com Building 10-A, Canal Town Industrial Park,...
  • Page 2: Table Of Contents

    CONTENT Copyright Statement This manual is under the copyright of Alpha ESS Co., Ltd, with all rights reserved. Please INTRODUCTION keep the manual properly and operate in strict accordance with all safety and operating 1.1 Brief Introduction instructions in this manual. Please do not operate the system before reading through the 1.2 Explanation of Terms...
  • Page 3: Introduction

    INTRODUCTION Introduction 1.1 Brief Introduction METER INSTRUCTION This manual applies for Storion-T50/T100 Li-ion battery energy storage system, mainly 6.1 Function Description includes: 6.2 Introduction 6.2.1. Introduction to the display interface (1) Safety introduction 6.2.2. Introduction to programming interface Introduces the product use, operating notes and qualification of operators of T50/T100 6.3 Meter setting...
  • Page 4: Safety Instructions

    INTRODUCTION SAFETY INSTRUCTIONS (3) Battery management system Safety Instructions Electronic equipment collection for monitoring the operating information of cells, packs and system units (such as voltage, current, temperature, protective parameter of 2.1 Keep the Manual batteries), evaluating the state of charge (SOC), the state of health (SOH) and cumulative This manual contains important information about operating the system.
  • Page 5: Setting Of Warning Sign For Safety

    SAFETY INSTRUCTIONS SAFETY INSTRUCTIONS 2.4 Setting of Warning Sign for Safety 2.10 Minimum Personal Protective Equipment To prevent erroneous operations and accidents caused by unrelated personnel nearby, For the safety of operators to the system, personal protective equipment are required. the suggestions below should be followed during the instruction, maintenance and During the operation, following protective equipment are required: repairing:...
  • Page 6: Ems Instruction

    EMS INSTRUCTION EMS INSTRUCTION 3.2 Introduction EMS Instruction If you find the manual content is inconsistent with the software version, please contact AlphaESS in time. 3.1 Function Description Main Interface displays the system working status and information, including: Power • Power: Total AC output power Pload 00.0kWh •...
  • Page 7: History

    EMS INSTRUCTION EMS INSTRUCTION Battery Ready Reserved BMS communication status CloseRelay Set whether to forcibly close the relay Network communication status Soc50Flag No used Battery Meter1 Grid meter communication status Set battery cluster ID (Only for M48112-S) Set ID Meter of PV inverter communication status Meter2 PCS communication status Export Control...
  • Page 8 EMS INSTRUCTION EMS INSTRUCTION Force Set whether to turn on the force GeneratorEN Set whether the DG function is turned on Charge charge function Set DG working mode to SOC Set whether to turn on the mode discharge time period function Generator- Allow Set DG working mode to time...
  • Page 9: Information

    EMS INSTRUCTION EMS INSTRUCTION Subnet Mask Set the subnet mask Set the AC power supply to the AC_Grid grid AC_Tied Default Set the default gateway AC_Gener- Gateway Set the AC power supply to DG ator Ethernet Set the MAC address, here is a fixed MAC Setting System Select inverter model, optional...
  • Page 10: Operation

    OPERATION OPERATION After the power is on, the LED on the batteries and HV900112 starts flashing. Operation D. After waiting for about 2 minutes, check the status of each HV900112 on the EMS display. You can check it according to the following table. If the value displayed on the EMS and the use in the table below, the battery output is normal.
  • Page 11: Power-Off Procedures

    OPERATION EMS OPERATION EMS operation Load Switch 5.1 Off-Grid Mode Grid/GEN Switch Check the settings on the TOP BMU box: A. Check the relay status of HV900112 : EMS->Status-> Battery->RelayL; B. Check the battery type : EMS->Setting->Function->Battery->M48112-S; C. Check the running mode is AC_Generator: EMS->Setting->Function->Pcs-> AC_Tied ->AC_Generator (Password :...
  • Page 12: Pmeteroffset Mode

    EMS OPERATION EMS OPERATION C. Check the running mode is AC_Grid: EMS->Setting->Function->PCS-> AC_Tied 5.2.2.1 Setting ->AC_Grid (Password : 1111); A. Turn on the function of Pmeteroffset: EMS->Setting-> Function->Grid-> D. Check the system software type : EMS->Setting->Function->Pcs->Minv->T50/T100; Pmeteroffset ->Enable->Yes; E. Check the STS status is enable : EMS->Setting-> Function->Backup-> BackupBox -> B.
  • Page 13: Time Period Charge And Discharge Mode

    EMS OPERATION METER INSTRUCTION 5.2.4. Time Period Charge and Discharge Mode Meter Instruction A.Turn on the function of force charge:EMS->Setting-> Function->System Mode-> Force Charge->Enable; 6.1 Function Description B. Set up the first charge start time: EMS->Setting-> Function->System Mode-> Charge Start Time 1; C.
  • Page 14: Introduction

    METER INSTRUCTION METER INSTRUCTION 6.2 Introduction 6.2.2. Introduction to programming interface 6.2.1. Introduction to the display interface 1.Press “SET” and the screen shows “PASS” 2.Press “ENT” and the screen shows “0000” Examples of display interface: 3.Input “0001” as the password and press “ENT” Table 4 Partial display interface diagram 4.Set the parameters 5.After settings, press “SET”...
  • Page 15: Setup In Ongrid Mode

    INSTALLATION EMERGENCY STOP 6.3.1. Setup in on-grid mode Emergency Stop Press "SET" to enter the programming interface; When the energy storage system is abnormal, you can press the emergency stop button Enter the password 0001 and press "Enter"; See "BUS1" and press "Enter"; "EPO"...
  • Page 16: Online Monitoring

    ONLINE MONITORING ONLINE MONITORING 8.2 Registering License Online Monitoring 8.1 Register You have to create a new account on our web server for the normal monitoring. So please use the following steps: Open the portal: www.alphaess.com. Enter the username and password, then click “Login” to jump to the home page. There will be a prompt after a failed login.
  • Page 17: Routine Maintenance

    ROUTINE MAINTENANCE ROUTINE MAINTENANCE 9.2.1. Routine inspection Routine maintenance 9.2.1.1 Power on inspection 9.1 Tool and Consumable Requirements List Operators need to conduct daily inspections of the equipment, and maintain the equipment by observing the status of the equipment indicator lights and software 9.1.1.
  • Page 18: Notes

    ROUTINE MAINTENANCE ROUTINE MAINTENANCE 9.2.1.2 Power off inspection The monitoring When the equipment has been running for a certain period of time, it is necessary to software can communicate with perform power outage maintenance on the equipment. Power outage maintenance Check if communication the PCS, and the Once 6...
  • Page 19 ROUTINE MAINTENANCE ROUTINE MAINTENANCE Check the fixation All battery fixing Once 6 Battery fixed Check whether the cable Once 6 bolts are tightened between the battery and Cable aging months No aging or damage is aging or damaged months the battery rack The rear surface of Check that the the front cover of...
  • Page 20 ROUTINE MAINTENANCE ROUTINE MAINTENANCE PCS switches, Check the LCD screen; Test PCS switch, Switches, contactors, circuit Simulate the power off and check whether the Once 6 months Security circuit contactor, circuit Once 12 breakers, and communication signal is available during the power breakers, breaker, protection protection...
  • Page 21 ROUTINE MAINTENANCE ROUTINE MAINTENANCE Shut down the system, and disconnected all the Perform routine maintenance on the fan to ensure Fan repair Once 6 months high-voltage control boxvoltage control box plastic that the fan operates normally, and dust the Whether the insulation cases.
  • Page 22 TROUBLESHOOTING TROUBLESHOOTING Troubleshooting Fault LCD Fault Fault Name Troubleshooting Category Display Fault LCD Fault Confirm that the ambient Fault Name Troubleshooting temperature is higher than -10℃.. Category Display If it is lower than it, please turn on the heating equipment such as Shut down the system for about Cell discharge heater.
  • Page 23: Troubleshooting

    DI1 (TOP BMU) interface Check if the communication cable terminal is connected tightly and connector between PCS restart the system. (Storion-T50/T100-INV: port 9, If the problem is not resolved, 10) and TOP BMU (EMS) is please contact AlphaESS connected and restart the system.
  • Page 24 TROUBLESHOOTING TROUBLESHOOTING Fault LCD Fault Fault LCD Fault Fault Name Troubleshooting Fault Name Troubleshooting Category Display Category Display Check if there is phase loss in the Check if DO2 (TOP BMU)is AC input of the inverter. If there connected properly, and after DC-AC subsystem AC_phase_lost is a phase loss, please power off...